3030A Specifications

Size:
  • 4” Wide ´ 8” Long ´ 1.75” Deep

    Weight:
  • Less than 2 pounds

    Operating Range:
  • 0 - 50 degrees C (32 - 122 degrees F)
  • Relative humidity to 70% (non-condensing)

    Power Requirement:
  • 12 VDC @ 50 mA, wall mount power supply included
        Internal Ni-Cad operates up to 10 hours after overnight charge

    Voltage:
  • Input Range:     1 - 600 Vrms steady-state (direct input),
                                or 600 – 5,000 Vrms with 5KVP probes,
                                or 600 – 15,000 Vrms with 15KVP probes.
  • Display Range:  1 - 6 megavolts (using input ratios)
  • Accuracy:         0.5%
  • Frequency Response:   No derating of accuracy for
                                harmonics through 25th harmonic (1500 Hz for
                                60 Hz fundamental)

    Current:
  • Input Range:     0.01 - 5000 Amps, AC or DC with the
                                proper current probe attached
                                With HA10: .01 - 10 Amps
                                With HA100: 0.1 - 100 Amps                             With HA1000: 1 - 1000 Amps                             With FX3000: 10 – 3000 Amps                             With FX5000: 100 - 5000 Amps                             With DC600: 5 - 600 Amps DC
                                6 autoranges
  • Display Range:  1ma - 6 megamps (using input ratios)
  • Accuracy:          0.5% plus accuracy of current probe
  • Frequency Response:    dependent on current probe attached                             With HA1000: no derating of accuracy for
                                harmonics through the 25th harmonic                             (1500 Hz for 60 Hz fundamental)







    Frequency:
  • Range:              DC, 45 - 66 Hz, 360 – 440 Hz fundamental
                                frequency
                                DC and 45 - 1650 Hz included in RMS
                                45 - 3000 Hz for harmonic measurements
  • Accuracy:         0.5%

    Power, Energy, Cost, Power Factor:
  • Display Range:   1 watt - 60 megawatts (using input ratios)
  • Accuracy:          1% plus accuracy of current probe

    Harmonic Distortion:
  • Range:              Range: Basic unit has THD only
                                With Harmonic Analysis Option, individual
                                harmonics through 15th (900 Hz)
                                With Harmonic Analysis and PowerSight
                                Manager software, harmonics through 50th
                                (3000 Hz)
  • Accuracy:          To within 1% of fundamental

    Transient Detection:
  • Minimum duration to guarantee capture: 32 msec
  • Measurable Range of Magnitude: ±2500 Vpk

    Captured Waveforms:
  • Quantity:          14 waveforms organized into 2 time-
                                coincident sets of 7 each (3 voltages and 4
                                currents)